Within the Ultracool Maxi range, there are four chillers with cooling outputs from 34.1 up to 64.4 kW which work with one single refrigeration circuit. The five models from 87.9 up to 265 kW of cooling capacities work with two independent refrigeration circuits to provide a backup security. All Maxi models are equipped with scroll compressors, work with R 407C as refrigerant and are suitable for outdoor installation. The internal pipes for the water circuit are made of PP-R (polypropylene random copolymer) and are thermowelded. Besides the main advantage that these connections are absolutely leak free, PP-R is corrosion and frost proof, allow for smaller pressure drops and are long lasting. The models UC-0300 to UC-0650 are also available as UC laser models with pre-configured options included.
Type: UC-0650
S/N: 67119
Technical Attributes Ultracool UC-0650 SP
Working temperature min. -5 °C
Working temperature max. 25 °C
Ambient temperature min. -15 °C
Ambient temperature max. 45 °C
Temperature stability 2 ±K
Cooling output at 25°C water outlet temperature 84.6 kW
Cooling output at 20°C water outlet temperature 84.6 kW
Cooling output at 15°C water outlet temperature 75.2 kW
Cooling output at 10°C water outlet temperature 64.4 kW
Cooling output at 5°C water outlet temperature 53.6 kW
Cooling output at 0°C water outlet temperature 43.9 kW
Cooling output at -5°C water outlet temperature 35.5 kW
Number of refrigeration circuits 1
Application: external
Power consumption 18.5 kW
Technical Attributes Ultracool UC-0650 SP
Pump pressure max. 4.7 bar
Pump pressure nominal 3.7 bar
Pump flow max. (pressure) 420 L/min
Pump flow nominal 196 L/min
Pump connection thread HT DN40
Volume water reservoir 300 L
Dimensions (WxDxH) in mm 1005 x 1565 x 1965
Noise level 59.2 dB(A)
Max. fuse 63 A